Rockwell-automation 1770-KF2 Data Highway or Highway Plus Interface Mo Bedienungsanleitung Seite 107

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 235
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 106
Message Packet Formats
Chapter 5
5-28
Physical Read
This command reads bytes of data from the PC data table or program
memory. Use this command to upload the contents of PLC-2 memory to
your computer.
Use the SIZE field to specify the number of bytes to be read. To specify a
number of PC words, SIZE should be an even value because PC words are
two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
04
SRCDST
TNSSTSCMD
44
SRCDST
ADDR
DATA
— Max. of 244 Bytes
SIZE
Physical Write
This command writes bytes of data into the PC data table or program
memory. Use this command to download the contents of a computer file
into PLC-2 memory.
Use the SIZE field to specify the number of bytes to be written. To
specify a number of PC words, SIZE should be an even value because PC
words are two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
03
SRCDST
TNSSTSCMD
43
SRCDST
ADDR
DATA
— Max. of 242 Bytes
Seitenansicht 106
1 2 ... 102 103 104 105 106 107 108 109 110 111 112 ... 234 235

Kommentare zu diesen Handbüchern

Keine Kommentare