Rockwell-automation 1769-HSC Compact High Speed Counter Module Bedienungsanleitung Seite 38

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 170
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 37
38 Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 2 Module Operation
Count Range
In a non-inverted count range, the outputs are active if the count value is within
the user-defined range. In an inverted count range, the outputs are active if the
count value is outside the user-defined range. Valid limits for the range are
-2…2 billion regardless of programmed minimum and maximum values.
Figure 9 shows all ranges referring to one counter. The module is capable of
individually assigning each range to any counter. Each counter can also have a
combination of count and rate ranges.
Figure 9 - Count Range Example
-200,000 106,000
0
Ctr[0].CurrentCount
Range 4
Stop Value
Range 1 Range 2 Range 4
Start Value
Output 0
Output 1
Output 2
Output 3
On
Off
Range 3
Table 9 - Count Range Example Values
Range
Range Counter Number
Range Type
(1)
Range Low Limit
Range High Limit
Range Invert Bit
Outputs
(2)
(Range[n].OutputControl word)
Outputs Affected
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1 01 0 -7000 -5000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0
2 01 0 -1000 4500 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1
3 01 0 -4000 3000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 2
4 01 0 -9000 9000 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 0 and 3
(1) For Range Type, 0 = count range and 1 = rate range.
(2) Bits 0…3 are real outputs. Bits 4…15 are virtual outputs.
Seitenansicht 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 169 170

Kommentare zu diesen Handbüchern

Keine Kommentare