Rockwell-automation 1763 MicroLogix 1100 Programmable Controllers User Bedienungsanleitung Seite 98

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 256
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 97
Publication 1763-UM001D-EN-P - March 2011
96 Communication Connections
Power Options
Below are two options for powering the AIC+:
Use the 24V DC user power supply built into the MicroLogix™ 1000,
1200, or 1500 controller. The AIC+ is powered through a hard-wired
connection using a communication cable (1761-CBL-HM02, or
equivalent) connected to port 2.
Use an external DC power supply with the following specifications:
operating voltage: 24V DC (-15%/+20%)
output current: 150 mA minimum
rated NEC Class 2
Make a hard-wired connection from the external supply to the screw
terminals on the bottom of the AIC+.
ATTENTION
If you use an external power supply, it must be 24V DC
(-15%/+20%). Permanent damage results if miswired with
the wrong power source.
Seitenansicht 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 255 256

Kommentare zu diesen Handbüchern

Keine Kommentare