MicroLogix 1762-OW8 Relay Output Module 13
Publication 1762-IN003B-EN-P - June 2013
Power supply distance rating 6
Isolated groups Group 1: Outputs 0…3
Group 2: Outputs 4…7
Output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec. or
2596V DC for 1 sec.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec. or
2596V DC for 1 sec.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor ID code 1
Product type code 7
Product code 120
Relay Contact Ratings
Volts (max.) Continuous
Amps per Point
(max.)
Amperes
(1)
(1)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
Voltamperes
Make Break Make Break
240V AC 2.5 A 7.5 A 0.75 A 1800 VA 180 VA
120V AC 15 A 1.5 A
125V DC 1.0 A
0.22 A
(2)
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58 A. For DC voltage applications less than 48V, the make/break rating
for relay contacts cannot exceed 2A.
28 VA
24V DC 2.0 A 1.2 A 28 VA
Output Specifications