Specifications
Input Specifications
Specification Value
Voltage Category
24V DC (Sink/Source)
(1)
(1) Sinking/Sourcing Inputs - Sinking/Sourcing describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices.
Operating Voltage Range 10…30V DC @ 30 °C (86 °F)
10…26.4V DC @ 65 °C (149 °F)
Number of Inputs 8
On-state Voltage, (Min) 10V DC
Off-state Voltage, (Max) 5V DC
On-state Current, (Min) 2.0 mA
Off-state Current, (Max) 1.5 mA
Inrush Current, (Max) 250 mA
Nominal Impedance 3 kΩ
Input Compatibility IEC Type 1+
Signal Delay Time, (Max) On-delay: 8 ms
Off-delay: 8 ms