
18 MicroLogix 1762-IF2OF2 Analog Input/Output Module
Publication 1762-IN005C-EN-P - July 2013
The bits are defined as follows:
• SIx = General status bits for input channels 0 and 1.
SOx = General status bits for output channels 0 and 1. This bit is set when an error
(over- or under-range) exists for that channel, or there is a general module hardware
error.
• OIx = Over-range flag bits for input channels 0 and 1.
OOx = Over-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.
• UIx = Under-range flag bits for input channels 0 and 1.
UOx = Under-range flag bits for output channels 0 and 1. These bits can be used in the
control program for error detection.
Output Data File
For each module, slot x, words 0 and 1 contain the channel output data.
Scaled-for-PID Format
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 Channel 0 Data 0…16,380 0 0
1 0 0 Channel 1 Data 0…16,380 0 0
2 reserved
3 reserved
4 reserved SO
1
SO
0
reserved SI
1
SI
0
5UI
0
OI
0
UI
1
OI
1
reserved U0
0
O0
0
U0
1
O0
1
reserved
Raw/Proportional Format
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 Channel 0 Data 0…32,760 0 0 0
1 0 Channel 1 Data 0…32,760 0 0 0
Scaled-for-PID Format
Word
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 Channel 0 Data 0…16,380 0 0
1 0 0 Channel 1 Data 0…16,380 0 0
Kommentare zu diesen Handbüchern