C–10
Instruction Valid Value
Ranges
Valid File TypesValid Addressing
Mode(s)
Instruction
Parameter
Description
MUL Multiply source A immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
source B immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
MVM Masked Move source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source mask immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
NEG Negate source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
NEQ Not Equal source A direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
source B immediate, direct,
indexed direct
O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max
NOT Logical NOT source direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
OR Logical OR source A direct, indexed direct O, I, S, B, T, C, R, N –32,768–32,767
source B direct, indexed direct O, I, S, B, T, C, R, N –32,768–32,767
destination direct, indexed direct O, I, S, B, T, C, R, N Not Applicable
OSR One–Shot Rising bit address direct O, I, S, B, T, C, R, N Not Applicable
OTE Output Energize bit address direct O, I, S, B, T, C, R, N Not Applicable
OTL Output Latch bit address direct O, I, S, B, T, C, R, N Not Applicable
OTU Output Unlatch bit address direct O, I, S, B, T, C, R, N Not Applicable
RAC HSC Reset
Accumulator
counter direct C Not Applicable
source immediate, direct O, I, S, B, T, C, R, N –32,768–32,767
f-min–f-max