SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 13
Publication 1747-IN019G-EN-P - December 2011
the update is complete, these four LED indicators remain on together. The download process of the
firmware takes approximately 3 minutes.
25. Open the AB_SNMP dialog box from the task bar if it does not appear automatically. Follow the
dialog box prompts to do the following:
•Verify the LEDs have stopped flashing.
Turn off power to the chassis.
Remove the processor.
ATTENTION: Do not remove the processor from the SLC 500 chassis until all
power is removed from the SLC 500 power supply.