Installation and Wiring
Publication
17466.8 - April 1997
Module Removal Procedure
1. Press the releases at the top and bottom of the module and slide
the module out of the chassis slot.
2. Cover all unused slots with the Card Slot Filler, Catalog Number
1746-N2.
The 1746-NI8 module contains an 18-position, removable terminal
block. The terminal pin-out is shown below.
!
ATTENTION: Disconnect power to the SLC before
attempting to install, remove, or wire the removable
terminal wiring block.
To avoid cracking the removable terminal block,
alternate the removal of the slotted terminal block
release screws.
Terminal Block
(Terminal Block Spare Part Catalog Number 1746RT25G)
Shield
Shield
Channel 0 (+)
Channel 1 (+)
Channel 2 (+)
Channel 3 (+)
Channel 4 (+)
Channel 5 (+)
Channel 6 (+)
Channel 7 (+)
Channel 0 (-)
Channel 1 (-)
Channel 2 (-)
Channel 3 (-)
Channel 4 (-)
Channel 5 (-)
Channel 6 (-)
Channel 7 (-)
Terminal Wiring