
Publication 1738-IN017B-EN-E - March 2005
ArmorPoint EtherNet/IP Adapter, Series A 11
PointBus Status Off Device not powered - check module status indicator.
Flashing Red/Green Recoverable fault has occurred:
- at power up, the number of expected modules does not equal
the number of modules present
- a module is missing
- node fault (I/O connection timeout).
Red Unrecoverable fault has occurred:
- the adapter is bus off
- controller in program/idle mode
- Ehternet cable open.
Green Adapter online with connections established (normal operation,
run mode).
System Power Off Not active - field power is off or dc-dc converter problem.
Green System power on - dc-dc converter active (5V).
Adapter Power Off Not active - field power is off.
Green Power on - 24V present.
Indication Indication Probable Cause
Kommentare zu diesen Handbüchern