16. Protection Features
Buer protection Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
in buer mode
typ. 58Vdc
max. 60Vdc
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output shuts
down and makes automatic restart attempts.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.5mm e.g. screws, small parts
Reverse polarity protection yes max. –35Vdc
Input over-voltages protection yes max. 35Vdc, no harm or defect to the unit
Internal fuse not included
17. Safety
Output voltage SELV IEC/EN 60950-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
Class of protection II
Isolation resistance > 5MOhm Power port to housing, 500Vdc
PE resistance < 0.1Ohm between housing and chassis ground terminal
Dielectric strength 500Vac Power port to signal port
500Vac Power port / signal port to housing
18. Certications
UL 508
IND. CONT. EQ.
18WM
LISTED E56639 for use in the U.S.A. (UL 508) and
Canada (C22.2 No. 14-95)
Industrial Control Equipment
UL 60950-1
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and
Canada (C22.2 No. 60950)
Information Technology Equipment, Level 3
EN 60950-1, EN 61204-3
Complies with CE EMC and CE Low Voltage Directives
GOST R GOST R certication is applicable for products intended for sale
and use within Russia. See below for link to the Certicate.
C-TICK C-Tick compliance is for products intended for sale and use within
the Australian market. See below for link to the C-Tick Declarations
of Conformity.
Kommentare zu diesen Handbüchern