Parameters B-27
1503-UM054C-EN-P – June 2013
Trip Coil Current for IntelliVAC Base Unit #3
[IB 3 Trip Current]
Parameter Number: 48,39,30,_,_.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-3-10
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the Trip
coil current on the IntelliVAC Basic Module #3. This coil current is
only valid for the first 200mS after the Trip c oil is energized.
Trip Coil Current for IntelliVAC Base Unit #4
[IB 4 Trip Current]
Parameter Number: 49,40,_,_,_.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-4-10
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the Trip
coil current on the IntelliVAC Basic Module #4. This coil current is
only valid for the first 200mS after the Trip coil is energized.