Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Bedienungsanleitung Seite 18

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 189
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 17
1-8
Product Overview
Protection and Diagnostics
(cont.)
Stall Protection and Jam Detection
The SMC Dialog Plus controller provides both stall protection and
jam detection for enhanced motor and system protection.
Stall protection is user-adjustable from 0.0 to 10.0 seconds (in
addition to the ramp time programmed).
Jam detection allows the user to determine the jam level (up to
999% of the motor’s FLC rating) and the delay time (up to 10.0
seconds) for application flexibility.
Figure 1.8 Stall Protection
Figure 1.9 Jam Detection
Jam detection is disabled during slow speed and braking operation.
Stall
600%
Percent
Full
Load
Current
Time (seconds)
Programmed Start Time
100%
Running Jam
Percent
Full
Load
Current
Time (seconds)
User Programmed Trip Level
Seitenansicht 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 188 189

Kommentare zu diesen Handbüchern

Keine Kommentare