Page
5
~
Flat Blade
Screwdriver
Fig.
2
-
4
2-8. Place accessory labels (supplied with kit) on circuit
breaker.
(See
Fig. 2-5.)
Note: Accessory labels show connection diagram for
shunt trip. Pigtail leads are color coded white and
yellow.
2
-
9
.
Test cutoff switch. Connect ohmmeter across pig
-
Screwdriver Depressing Shunt Trip Solenoid
Plunger
tail leads or terminal block connections. Check
continuity as follows:
a. Circuit breaker handle OFF
.- no continuity.
b. Circuit breaker handle
ON
-
less than
9000
ohms.
Terminal Block
Connection Diagram
Label (When Used)
Identification
Label
Pigtail
Diagram
(When Used)
Fig.
2
-
5
Preferred Mounting Locations for Accessory
Nameplate Labels
Note: For molded case switches, omit step
c.
c. Press PUSH
-
TO
-
TRIP button
-
no continuity.
d. If cutoff switch fails test, make sure that shunt
trip module is properly seated in trip unit slots.
If
problem persists, contact Allen-Bradley.
2
-
1 0. Install circuit breaker.
2
-
11. Connect shunt trip as required (see Fig. 2
-
6).
Allen-
Bradley assumes no responsibility for malfunc
-
tioning accessories installed improperly by the customer.