Publication 1405-IN002C-EN-P - November 2004
10 Bulletin 1405 (M620) Operating Instructions
Analog outputs selected as ‘I’, ‘=’, ‘P’ or ‘S’ provide a linear
measurement scaled from zero to the full-scale value as configured by
the V
nominal
and I
nominal
settings.
Refer to Table 4 and Table 5 for more information.
With the output range set to 0 to 20 mA, the relationships are:
Table 4
Line-to-line voltages (V
L-L
)
for 0 to 20 mA Range
10 mA V V
nom
⁄()1–()4 10 mA••+
Line-to-neutral voltages (V
L-N
)
for 0 to 20 mA Range
10 mA 3() VV
nom
⁄()1–()4 10 mA•••+
Currents
20 mA I I
nominal
ڥ
Power (per phase)
20 mA PX V
nominal
3I
nominal
•⁄()⁄•
Total power
20 mA P V
nominal
I
nominal
3••()⁄•
Power factor
10 mA 10 mA 1 Cos f–()0.5 (capacitive⁄()•+
10 mA 10 mA 1 Cos f–()0.5 (inductive⁄()•–
With the output range set to 4 to 20 mA, the relationships are:
Table 5
Line-to-line voltages (V
L-L
)
4 mA 8 mA V V
nom
⁄()1–()48 mA••++
Line-to-neutral voltages (V
L-N
)
4 mA 8 mA 3() VV
nom
⁄()1–()48 mA•••++
Currents
4 mA 16 mA I I
nominal
ڥ+
Power (per phase)
4 mA 16 mA PX V
nominal
3I
nominal
•⁄()⁄•+
Total power
20 mA P V
nominal
I
nominal
3••()⁄•
Power factor
4 mA 8 mA 8 mA 1 Cos f–()0.5 (capacitive)⁄•++
4 mA 8 mA 8 mA 1 Cos f–()0.5 (inductive)⁄•–+