Chapter 5
Configuration and Interfacing
5-5
Table 5.D
Data Table Structure for SLC-500 Style Addressing
Parameter
Number
SLC-500 Style Address
Description of
Location’s Purpose
1 – 249 N50:1 – 249
250 – 499 N51:0 – 249
500 – 749 N52:0 – 249 Parameter
Value
9250 – 9499 N87:0 – 249 Read or Write
9500 – 9749 N88:0 – 249
9750 – 9999 N89:0 – 249
N20:0 – 127 Status of Last Parameter Write
1 – 249 N90:1 – 249
250 – 499 N91:0 – 249
500 – 749 N92:0 – 249 Parameter
Read
9250 – 9499 N127:0 – 249 Full
9500 – 9749 N128:0 – 249
9750 – 9999 N129:0 – 249
N40:0 – 63 Block Transfer Emulation Area
N41:0 Logic Command/Status
N41:1 Reference/Feedback
N41:2 Datalink A1
N41:3 Datalink A2
N41:4 Datalink B1
N41:5 Datalink B2
N41:6 Datalink C1
N41:7 Datalink C2
N41:8 Datalink D1
N41:9 Datalink D2
N42:0 #ENQs
N42:1 #NAKs
N42:2 Message TIMEOUT (mS)
N42:3 Application TIMEOUT (Seconds)
or N200:0 – 63 System Area
NOTE: The address locations shown in this table are not limited to SLC
commands and may be used by any device capable of generating them.