AN-T80017
Issue 2 June 08 AN-T80017 1
Application Note
Regent to Trusted Migration
This document describes the steps needed to replace a Regent processor chassis with a Trusted
processor chassis. This replaces the Regent processor and communications modules and providing a
future path to expansion of the Trusted system side. It assumes a knowledge of Trusted application
design.
Issue Record
Issue
Number
Date Revised by Technical
Check
Authorised by Modification
1 June 08 Nick Owens Andy Holgate Pete Stock Initial Issue
2 June 08 Nick Owens Andy Holgate Pete Stock Corrections
Seitenansicht 0
1 2 3 4 5 6 ... 22 23

Inhaltsverzeichnis

Seite 1 - Application Note

TrustedTM AN-T80017 Issue 2 June 08 AN-T80017 1 Application Note Regent to Trusted Migration This document describes the steps needed to replace

Seite 2 - 1. Hardware

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 10 5. Application Examples Figure 3 Regent I/O Module Configuration Reg

Seite 3 - 1.1. Parts List

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 11 In Trusted, all variables must be named in the dictionary and then co

Seite 4 - 2. Electrical

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 12 The Regent multiplexer module is a special case. This has multiple su

Seite 5

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 13 The Trusted implementation for multiplexed I/O is to use many separat

Seite 6 - 3. Installation

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 14 Regent variables can be declared in the Shared Variables lists as Con

Seite 7 - 4. Application

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 15 Winterpret shared registers and shared floating point registers are i

Seite 8

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 16 Winterpret allows multiple programs, each containing function blocks

Seite 9

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 17 Regent ladder logic function blocks are on a fixed grid with 10 colum

Seite 10 - 5. Application Examples

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 18 Regent is capable of floating point arithmetic in separate Math funct

Seite 11

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 19 Regent has scaling functions as a separate function block language. T

Seite 12

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 2 1. Hardware The migration principles are identical for Regent (panel m

Seite 13

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 20 Regent has a separate function block language for defining points to

Seite 14

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 21 Communication settings are very different, by definition of the diffe

Seite 15 - Figure 8 Analogue variables

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 22

Seite 16

ICS Triplex technologies and services are available worldwide. Hall Road Maldon Essex CM9 4LA UK Tel: +44 1621 854444 Fax: +44 1621 851531 www.ics

Seite 17

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 3 1.1. Parts List T8100 1off Processor Chassis T8270 1off Fan Tray

Seite 18

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 4 2. Electrical The chassis and its modules are powered from a dual 24Vd

Seite 19 - Figure 12 Scaling functions

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 5 Figure 2 Example Power Supply Overview

Seite 20 - Figure 13 Sequence of Events

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 6 3. Installation Both the Regent and Trusted are 3-2-0 degradation syst

Seite 21

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 7 4. Application There is no automated tool for application conversion f

Seite 22

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 8 Channel LEDs may be prevented from showing faults using the MONITOR_MA

Seite 23

TrustedTM AN-T80017 Regent to Trusted Migration Issue 2 June 08 AN-T80017 9 4.6. FLOAT function blocks These are very similar to Trusted structure