10 ArmorBlock MaXum 8 Input / 8 Output Module Series B
Publication 1792D-IN020B-EN-P - September 2000
Troubleshoot with the Indicators
This module has the following indicators:
Network and Module status indicator
Logic status indicator
Auxiliary Power indicator
Individual I/O status indicators for inputs 0 through 7 and
outputs 0 through 7.
The following table describes network and module status indicators.
Net/Mod Status Indicator
Indicator Status
Off No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green On line, link OK, connected
Flashing Red Recoverable fault - module configuration error
I/O connection fault - one or more I/O connections in the timed-out
state
41517
Point indicators for
inputs 0 and 1
Module Status
Indicators
Connector A
Connector B
Connector C
Connector D
Connector E
Connector F
Connector G
Connector H
Point indicators for
inputs 2 and 3
Point indicators for
inputs 4 and 5
Point indicators for
inputs 6 and 7
Point indicators for
outputs 6 and 7
Point indicators for
outputs 4 and 5
Point indicators for
outputs 2 and 3
Point indicators for
outputs 0 and 1
LED Assignments