ICS Regent
®
PD
-
6035
Industrial Control Services
1
Multiplexed I/O Modules
(T3491)
Issue 1,
March, 06
Multiplexed I/O modules provide two RS
-
422 serial port
interfaces between the Regent system and ICS’s remote
multiplexed I/O Unit (MIU) equipment, providing an
economical interface to digital inputs and outputs. MIU
equipment is often used for matrix and mimic displays in
safety and fire and gas systems or low cost, remote simplex
input and outputs.
Features
Occupies one slot in the I/O chassis.
Two isolated RS
-
422 serial ports for remote multiplexed I/O.
Supports up to 512 digital inputs and 256 digital outputs of
remote MIU equipment.
·
Individual front panel indicators on each module show module
active and fault status; and transmit, receive and fault status
for each port.
Serial ports can be used in simplex or duplex modes (with
2oo2 testing in dual mode).
·
1000 volt minimum electrical isolation between serial ports
and between serial and logic circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Multiplexed I/O mo
dules support multi
-
drop connection to
remote MIU equipment up to 4000 feet (1220 meters) away at
19200 baud. The two serial ports of the Mux I/O module can
be configured for simplex or duplex mode. In duplex mode,
2oo2 voting is performed on the I/O data.
Seitenansicht 0
1 2 3 4 5 6 ... 18 19

Inhaltsverzeichnis

Seite 1 - ICS Regent

ICS Regent® PD-6035 Industrial Control Services 1 Multiplexed I/O Modules (T3491) Issue 1, March, 06 Multiplexed I/O modules provide two RS-422 se

Seite 2 - Module Operation

Multiplexed I/O Module (T3491) 10 Industrial Control Services different module type. Figure 5 illustrates how the slot keys are installed on the

Seite 3 - Testing and Diagnostics

Multiplexed I/O Module (T3491) PD-6035 Mar-06 11 Table 1. Slot Key Positions. Module Upper Connector Lower Connector T3491 4 2 Fault Mode Jumper

Seite 4

Multiplexed I/O Module (T3491) 12 Industrial Control Services Figure 6. The Matrix Interface Module Dialog. 3) Define the MIU Processors: After

Seite 5

Multiplexed I/O Module (T3491) PD-6035 Mar-06 13 through 15). You may also enter a description to annotate the MIU processor definition. Each MI

Seite 6

Multiplexed I/O Module (T3491) 14 Industrial Control Services Figure 9. The Mux Input Unit and Mux Output Unit Dialog Boxes. 5) Edit each poin

Seite 7

Multiplexed I/O Module (T3491) PD-6035 Mar-06 15 Figure 10. The Mux Input Point and Mux Output Point Dialog Boxes. Name Also called the tag n

Seite 8 - Serial Port Cable Connections

Multiplexed I/O Module (T3491) 16 Industrial Control Services configuration and also when you load the application program that controls the outpu

Seite 9

Multiplexed I/O Module (T3491) PD-6035 Mar-06 17 Maintenance No periodic maintenance or calibration is required for the multiplexed I/O module.

Seite 10 - Industrial Control Services

Multiplexed I/O Module (T3491) 18 Industrial Control Services Specifications Safetybus Power 1.0 load units Mux I/O Capacity Maximum 12 MIU proces

Seite 11

Multiplexed I/O Module (T3491) PD-6035 Mar-06 19 Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm S

Seite 12

Multiplexed I/O Module (T3491) 2 Industrial Control Services The following MIU equipment may be interfaced to the Multiplexed I/O Module · MIU32

Seite 13

Multiplexed I/O Module (T3491) PD-6035 Mar-06 3 Figure 2. Block Diagram of Multiplexed I/O Module. The Voter, FPGA and triple buffers provid

Seite 14 - Important!

Multiplexed I/O Module (T3491) 4 Industrial Control Services Standard Module Testing Each module’s voter circuits are periodically tested by the

Seite 15

Multiplexed I/O Module (T3491) PD-6035 Mar-06 5 Front Panel Indicators Figure 3 shows the physical features of the Mux I/O module. The front pa

Seite 16 - Programming

Multiplexed I/O Module (T3491) 6 Industrial Control Services Figure 3. Multiplexed I/O Module.

Seite 17 - Safety Considerations

Multiplexed I/O Module (T3491) PD-6035 Mar-06 7 Active and Fault Status Indicators These green and red LEDs indicate the overall health of the M

Seite 18 - Specifications

Multiplexed I/O Module (T3491) 8 Industrial Control Services When output data changes state, the Mux I/O module writes the output data to both po

Seite 19

Multiplexed I/O Module (T3491) PD-6035 Mar-06 9 Figure 4. MUX I/O Module Serial Cable Connections. Keying The I/O chassis can be physically